Date: 12 July 2026
Environment: Windows, .NET 8 Release build, isolated laboratory IED network
Client: ARIEC61850 IED Discovery Smart Control Tester
The native control request path was exercised against a real laboratory IED. A command selected from the Smart Control Tester reached the IED through the ARIEC61850 control stack after live discovery of the control object.
This record intentionally avoids publishing customer, site, IP-address, serial-number, vendor, and firmware details. Those details should remain in a private test report when required for project acceptance.
- Release solution build completed on the Windows test workstation.
- IED association and live model discovery completed.
- A controllable Data Object based on
CSWI.Poswas opened through the native control service. - The tester presented operator intent as OPEN/CLOSE rather than exposing raw
Oper,SBO, orSBOwwrites. - The command request traversed the ARIEC61850 live control path and reached the IED.
- The UI and engine retained protocol evidence for diagnosis.
This single live test does not establish:
- formal IEC 61850 conformance;
- interoperability with every IED vendor, model, or firmware release;
- successful coverage of all four control models;
- every negative CommandTermination and AddCause path;
- long-duration repeated-operation reliability;
- operational-substation safety approval;
- process movement unless independently verified by status, indications, and the approved test procedure.
Record the following before describing an IED family as validated:
- IED vendor, model, firmware, SCL revision, and test date in a private report.
- Control Data Object, CDC, discovered
ctlModel, and liveOper/SBOw/Canceltype signatures. - Initial status value and quality.
- Origin category and Orig ID accepted by the IED.
- Interlock, synchrocheck, and Test settings.
- Request, immediate MMS response, CommandTermination, LastApplError, ControlError, and AddCause evidence.
- Final status value and independent process indication.
- SBO timeout and explicit Cancel behavior where applicable.
- Association-loss and competing-client behavior.
- Repeated OPEN/CLOSE cycles within the approved laboratory procedure.
Recommended public wording:
The ARIEC61850 Smart Control Tester has completed an end-to-end command path with a laboratory IED. Multi-vendor validation and formal conformance testing remain ongoing.
Avoid wording that implies certification, universal interoperability, or permission for unrestricted field operation.